Professional Design Air Treatment Unit - E140 SERIES PRESSURE REGULATORS – Ainuo Technology
Short Description:
BALANCED VALVE FULL SEAL AT ZERO FLOW OPTIONAL MAXIMUM AND/OR MINIMUM PRESSURE SLAM-SHUT VALVE WIDE OUTLET-PRESSURE REGULATION RANGE ACCURATE PRESSURE REGULATION E140 serials regulator is a diaphragm and spring controlled direct acting regulator.Widely used in medium-sized commercial facilities and regional.Built-in with relief valve and ultra low-pressure safety devices.The regulator has characteristics of simple structure,convenient operation,easy maintenance online,etc. TECHNICAL ...
Professional Design Air Treatment Unit - E140 SERIES PRESSURE REGULATORS – Ainuo Technology Detail:
BALANCED VALVE
FULL SEAL AT ZERO FLOW
OPTIONAL MAXIMUM AND/OR MINIMUM PRESSURE SLAM-SHUT VALVE
WIDE OUTLET-PRESSURE REGULATION RANGE
ACCURATE PRESSURE REGULATION
E140 serials regulator is a diaphragm and spring controlled direct acting regulator.Widely used in medium-sized commercial facilities and regional.Built-in with relief valve and ultra low-pressure safety devices.The regulator has characteristics of simple structure,convenient operation,easy maintenance online,etc.
TECHNICAL DATA
Inlet pressure | Pemax.≤6 bar | |
Shut-off when over-pressure | Who:22.5-450 mbar | |
Inlet pressure range | Bpe: 0.5-5 bar | |
Shut-off when low-pressure | Whu:12.8-250 mbar | |
Outlet pressure set range | standard | Wh: 15-70 mbar |
HP | Wh:70-300 mbar | |
Shut-off accuracy | AG: ≤5% | |
Accuracy class | AC: ±5% | |
Response time | Ta: ≤1 sec | |
Shut-off pressure class | SG: +10% | |
Flow rate (natural gas) | Qmax. ≤900Nm³/h | |
Operating temprature | -20℃-60℃ | |
Connection size | DN50 PN16 | |
Ambient temperature | -30℃-60℃ | |
Weight | Low pressure type:19kgHigh pressure type:21kg |
CAPACITY CHART
Outletpressure
(mbar) |
Inlet pressure (bar) | ||||||||||||||
0.05 | 0.07 | 0.1 | 0.15 | 0.2 | 0.3 | 0.4 | 0.5 | 0.75 | 1 | 1.5 | 2 | 3 | 4 | ||
STANDARD | 15 | 80 | 100 | 120 | 150 | 170 | 220 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 |
20 | 75 | 100 | 120 | 150 | 170 | 220 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 | |
30 | 60 | 90 | 110 | 150 | 170 | 220 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 | |
40 | - | 80 | 100 | 140 | 170 | 210 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 | |
50 | - | 70 | 90 | 140 | 160 | 210 | 240 | 270 | 340 | 400 | 500 | 600 | 650 | 750 | |
75 | - | - | 70 | 90 | 150 | 200 | 240 | 270 | 340 | 400 | 500 | 600 | 650 | 750 | |
AP |
100 | - | - | - | - | 140 | 190 | 230 | 250 | 340 | 400 | 500 | 600 | 650 | 750 |
150 | - | - | - | - | 100 | 170 | 220 | 250 | 330 | 390 | 500 | 600 | 650 | 750 | |
200 | - | - | - | - | - | 140 | 200 | 240 | 310 | 380 | 500 | 600 | 650 | 750 | |
300 | - | - | - | - | - | - | 150 | 210 | 310 | 380 | 500 | 600 | 650 | 750 |
Capacities (cu.m./hr) are applicable to natural gas with a specific gravity of 0.702. For other gases, the values shown in the chart below must be multiplied by 0.595 for propane, 0.518 for butane, 0.755 for nitrogen and 0.744 for air.
OUTLINE DIMENSIONS (mm)
Product detail pictures:
Related Product Guide:
3 Basic Elements to Know About Your Gas Regulator
How to Use LPG Gas Regulators
Our goal is usually to deliver high quality items at aggressive price ranges, and top-notch service to shoppers around the entire world. We're ISO9001, CE, and GS certified and strictly adhere to their high quality specifications for Professional Design Air Treatment Unit - E140 SERIES PRESSURE REGULATORS – Ainuo Technology, The product will supply to all over the world, such as: Marseille , Angola , Vancouver , Many products fully conform to the most rigorous of international guidelines and with our first-rate delivery service you will have them delivered at any time and in any place. And because Kayo deals in the entire spectrum of protective equipment, our customers don't need to waste time shopping around.
By Doris from Salt Lake City - 2015.11.22 12:28
The product manager is a very hot and professional person, we have a pleasant conversation, and finally we reached a consensus agreement.
By Marjorie from Rwanda - 2016.09.22 11:32