Short Description:
BALANCED VALVE FULL SEAL AT ZERO FLOW OPTIONAL MAXIMUM AND/OR MINIMUM PRESSURE SLAM-SHUT VALVE WIDE OUTLET-PRESSURE REGULATION RANGE ACCURATE PRESSURE REGULATION E140 serials regulator is a diaphragm and spring controlled direct acting regulator.Widely used in medium-sized commercial facilities and regional.Built-in with relief valve and ultra low-pressure safety devices.The regulator has characteristics of simple structure,convenient operation,easy maintenance online,etc. TECHNICAL ...
Super Purchasing for Fixed Orifice Gas Regulator - E140 SERIES PRESSURE REGULATORS – Ainuo Technology Detail:
BALANCED VALVE
FULL SEAL AT ZERO FLOW
OPTIONAL MAXIMUM AND/OR MINIMUM PRESSURE SLAM-SHUT VALVE
WIDE OUTLET-PRESSURE REGULATION RANGE
ACCURATE PRESSURE REGULATION
E140 serials regulator is a diaphragm and spring controlled direct acting regulator.Widely used in medium-sized commercial facilities and regional.Built-in with relief valve and ultra low-pressure safety devices.The regulator has characteristics of simple structure,convenient operation,easy maintenance online,etc.
TECHNICAL DATA
| Inlet pressure | Pemax.≤6 bar | |
| Shut-off when over-pressure | Who:22.5-450 mbar | |
| Inlet pressure range | Bpe: 0.5-5 bar | |
| Shut-off when low-pressure | Whu:12.8-250 mbar | |
| Outlet pressure set range | standard | Wh: 15-70 mbar |
| HP | Wh:70-300 mbar | |
| Shut-off accuracy | AG: ≤5% | |
| Accuracy class | AC: ±5% | |
| Response time | Ta: ≤1 sec | |
| Shut-off pressure class | SG: +10% | |
| Flow rate (natural gas) | Qmax. ≤900Nm³/h | |
| Operating temprature | -20℃-60℃ | |
| Connection size | DN50 PN16 | |
| Ambient temperature | -30℃-60℃ | |
| Weight | Low pressure type:19kgHigh pressure type:21kg | |
CAPACITY CHART
| Outletpressure
(mbar) |
Inlet pressure (bar) | ||||||||||||||
| 0.05 | 0.07 | 0.1 | 0.15 | 0.2 | 0.3 | 0.4 | 0.5 | 0.75 | 1 | 1.5 | 2 | 3 | 4 | ||
| STANDARD | 15 | 80 | 100 | 120 | 150 | 170 | 220 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 |
| 20 | 75 | 100 | 120 | 150 | 170 | 220 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 | |
| 30 | 60 | 90 | 110 | 150 | 170 | 220 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 | |
| 40 | - | 80 | 100 | 140 | 170 | 210 | 250 | 280 | 340 | 400 | 500 | 600 | 650 | 750 | |
| 50 | - | 70 | 90 | 140 | 160 | 210 | 240 | 270 | 340 | 400 | 500 | 600 | 650 | 750 | |
| 75 | - | - | 70 | 90 | 150 | 200 | 240 | 270 | 340 | 400 | 500 | 600 | 650 | 750 | |
|
AP |
100 | - | - | - | - | 140 | 190 | 230 | 250 | 340 | 400 | 500 | 600 | 650 | 750 |
| 150 | - | - | - | - | 100 | 170 | 220 | 250 | 330 | 390 | 500 | 600 | 650 | 750 | |
| 200 | - | - | - | - | - | 140 | 200 | 240 | 310 | 380 | 500 | 600 | 650 | 750 | |
| 300 | - | - | - | - | - | - | 150 | 210 | 310 | 380 | 500 | 600 | 650 | 750 | |
Capacities (cu.m./hr) are applicable to natural gas with a specific gravity of 0.702. For other gases, the values shown in the chart below must be multiplied by 0.595 for propane, 0.518 for butane, 0.755 for nitrogen and 0.744 for air.
OUTLINE DIMENSIONS (mm)
Product detail pictures:

Related Product Guide:
3 Basic Elements to Know About Your Gas Regulator
How to Use LPG Gas Regulators
Sticking to the belief of "Creating products of high quality and making friends with people from all over the world", we always put the interest of customers in the first place for Super Purchasing for Fixed Orifice Gas Regulator - E140 SERIES PRESSURE REGULATORS – Ainuo Technology, The product will supply to all over the world, such as: Qatar , Costa Rica , Oman , We only supply quality products and we believe this is the only way to keep business continue. We can supply custom service too such as Logo, custom size, or custom products etc that can according to customer's requirement.